FLD 90T tester is engineered to measure the dielectric strength of transformer oil and other insulating fluids in compliance with IEC 60156, ASTM D877, and ASTM D1816 standards. This is high-performance device with a test voltage up to 90 kV.

 

This fully automated Fluidex’s tester facilitates testing in accordance with the specified procedures outlined in these standards, as well as custom user-defined procedures accessible through the setup menu.

Fluidex FLD 90T Oil Breakdown Voltage Dielectric Tester 90kV

  • Parameter

    Value

    1 Operating AC voltage (internal rechargable battery 12V 7.2Ah), V

    85–264

    2 Power frequency, Hz

    48–63

    3 Power requirement, VA

    70 max

    4 Max voltage output, kV

    Sinusoidal, up to 90 kV

    5 Output voltage measurement accuracy

    ±1 %

    6 Voltage increase rate, kV/sec

    0.5 to 10

    7 Resolution of output voltage indication, V

    100

    8 High voltage timeout after breakthrough, μs

    10 max, 4 typical

    9 Measuring cell volume, in3 (cm3)

    30 (500)

    10 Temperature measurement range, °F (°С)

    32–212 (0–100)

    11 Temperature measurement resolution, °F (°С)

    32.18 (0.1)

    12 Inbuilt printer & USB

    Yes

    13 Operating temperature , °F (°С)

    14–122 (-10–50)

    14 Storage temperature, °F (°С)

    From -4 to + 140 (from -20 to 60)

    15 Relative humidity, %

    Up to 90 without condensation

    16 Dimensions, in (mm)

    20/12/13 (510/300/334)

    17 Weight, lbs (kg), max

    66 (30)